Motor circuit breaker, TeSys GV3, 3P, 30-40 A, thermal magnetic, EverLink terminals, [In] rated current 40 A, Thermal protection adjustment range, 30…40 A conforming to IEC 60947-4-1, Magnetic tripping current, 560 A, [Ith] conventional free air thermal current, 40 A conforming to IEC 60947-4-1, [Ue] rated operational voltage, 690 V AC 50/60 Hz conforming to IEC 60947-2, [Ui] rated insulation voltage, 690 V AC 50/60 Hz conforming to IEC 60947-2, [Uimp] rated impulse withstand voltage, 6 kV conforming to IEC 60947-2, Phase failure sensitivity, Yes conforming to IEC 60947-4-1, Suitability for isolation, Yes conforming to IEC 60947-1, Power dissipation per pole, 8 W, Include: Wöhner Eques easyconnector 63a – 32459, EAN: 4021267324599. Motor circuit breaker TeSys GV3 3P 30-40 A Thermal magnetic EverLink terminals [In] rated current 40 A Thermal protection adjustment range, 30â¦40 A conforming to IEC 60947-4-1 Magnetic tripping current, 560 A [Ith] conventional free air thermal current, 40 A conforming to IEC 60947-4-1 [Ue] rated operational voltage, 690 V AC 50/60 Hz conforming to IEC 60947-2 [Ui] rated insulation voltage, 690 V AC 50/60 Hz conforming to IEC 60947-2 [Uimp] rated impulse withstand voltage, 6 kV conforming to IEC 60947-2 Phase failure sensitivity, Yes conforming to IEC 60947-4-1 Suitability for isolation, Yes conforming to IEC 60947-1 Power dissipation per pole, 8 W Include: Wöhner Eques easyconnector 63a – 32459, EAN: 4021267324599 GV3P40 + 32459 + 32459 Wöhner is the item offered by Wöhner that is ideal for industrial applications. This item can be purchased at PLC2Day.